Recommended Practices for the Testing and Verification of Spill, Overfill, LeakDetection and Secondary Containment Equipment at UST Facilities APPENDIX C-7
OPERATION INSPECTION
Facility Name: Sirmola Agency
Owner:Westonik web solution
Address:3902/A New Street, Sirmola North korea
Address:
City, State, Zip Code:Ketchikan, Alaska, 99950
City, State, Zip Code:, , 46554
Facility I.D. #:Test2
Phone #:219-210-0052
Testing Company: Midwest Ecs LLC
Phone #:219-210-0622
Date:12/09/2023
This procedure is to determine whether the automatic tank guage (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the inspection procedure. This procedure is applicable to tank level monitor stems that touch the bottom of the tank when in place.
Tank Number
Product Stored
ATG Brand and Model
1. Tank Volume, gallons
2. Tank Diameter, inches
3. After removing the ATG from the tank, it has been inspected and any damaged or missing parts replaced?
4. Float moves freely on the stem without binding?
Yes
No
Yes
No
5. Fuel float level agrees with the value pro- grammed into the console?
Yes
No
Yes
No
6. Water float level agrees with the value pro- grammed into the console?
Yes
No
Yes
No
7. Inch level from bottom of stem when 90% alarm is triggered.
8. Inch level at which the overfill alarm activates corresponds with value programmed in the gauge?
Yes
No
Yes
No
9. Inch level from the bottom when the water float first triggers an alarm.
10. Inch level at which the water float alarm acti- vates corresponds with value programmed in the gauge?
Yes
No
Yes
No
If any answers in Lines 3, 4, 5, or 6 are “No,” the system has failed the test.
Pass
Fail
Pass
Fail
Tester’s Signature